Operating instructions
S3G800-BV01-01
Translation of the original operating instructions
4.5 Connection screen
No. Conn. Designation Function / assignment
KL 1 1 L1 Mains supply connection, supply voltage 3~380-480 VAC; 50/60 Hz
KL 1 2 L2 Mains supply connection, supply voltage 3~380-480 VAC; 50/60 Hz
KL 1 3 L3 Mains supply connection, supply voltage 3~380-480 VAC; 50/60 Hz
PE PE Earth connection, PE connection
KL 2 1 NO Status relay, floating status contact; normally open; close with error
KL2 2 COM Status relay; floating status contact; changeover contact; common connection; contact rating 250 VAC / max.
2 A (AC1) / min. 10 mA
KL2 3 NC Status relay, floating status contact; break with error
KL 3 1 RSA Bus connection RS-485, RSA, MODBUS RTU; SELV
KL 3 2 RSB Bus connection RS-485, RSB, MODBUS RTU; SELV
KL 3 3 / 10 GND Signal ground for control interface; SELV
KL 3 4 Ain1 U Analogue input 1, set value: 0-10 V, Ri = 100 kΩ, parametrisable curve, only usable as alternative to input
Ain1; SELV
KL 3 5 + 10 V Fixed voltage output 10 VDC, +10 V ±3%, max. 10 mA, short-circuit-proof, power supply for external
devices (e.g. potentiometer), SELV
KL 3 6 Ain1 I Analogue input 1, set value: 4-20 mA; Ri = 100 Ω, parametrisable curve, only usable as alternative to input
Ain1 U; SELV
KL 3 7 Din1 Digital input 1: enabling of electronics,
enabling: open pin or applied voltage 5-50 VDC
disabling: bridge to GND or applied voltage <1 VDC
reset function: triggers software reset after a level change to <1 VDC; SELV
KL 3 8 Din2 Digital input 2: parameter set switch 1/2, according to EEPROM setting, the valid/used parameter set can be
selected via bus or via digital input DIN2.
Parameter set 1: open pin or applied voltage 5-50 VDC
Parameter set 2: bridge to GND or applied voltage <1 VDC; SELV
KL 3 9 Din3 Digital input 3: controller function of integrated controller, according to EEPROM setting, the controller function
of the integrated controller is normally/inversely selectable per bus or per digital input
normal: open pin or applied voltage 5-50 VDC
inverse: bridge to GND or applied voltage <1 VDC; SELV
KL 3 11 Ain2 U Analogue input 2, actual value: 0-10 V, Ri = 100 kΩ, parametrisable curve, only usable as alternative to input
Ain2; SELV
KL 3 12 + 20 V Fixed voltage output 20 VDC, +20 V +25/-10%, max. 50 mA, short-circuit-proof, power supply for external
devices (e.g. sensors); SELV
KL 3 13 Ain2 I Analogue input 2, actual value: 4-20 mA, Ri = 100 Ω, parametrisable curve, only usable as alternative to
input Ain2 U; SELV
KL 3 14 Aout Analogue output 0-10 VDC, max. 5 mA, output of the current motor level control coefficient / motor speed
parametrisable curve; SELV
Item no. 50139-5-9970 · ENG · Revision 82539 · Release 2014-05-08 · Page 9 / 12